科技报告详细信息
Phased Startup Initiative Phase 3 and 4 Test Procedure (OCRWM)
PAJUNEN, A.L.
Fluor Hanford, Inc.
关键词: Removal;    Fuel Storage Pools;    Water Treatment;    Water Quality;    Scrap Metals;   
DOI  :  10.2172/804494
RP-ID  :  SNF-5952, Rev.1
RP-ID  :  AC06-96RL13200
RP-ID  :  804494
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

The purpose of this test procedure is to safely operate the Fuel Retrieval System (FRS) and Integrated Water Treatment System (IWTS) with specific fuel canisters, and show that canisters containing fuel can be retrieved from the canister queue, decapped in the Canister Decapper, and loaded into the Primary Clean Machine (PCM) for fuel cleaning; and that fuel can be sorted on the Process Table, then loaded back into fuel canisters and relocated in basin storage. An option is included to load selected elements into multi-canister overpack (MCO) Fuel Baskets. Additional Data are collected during this test, beyond that collected during production operations. These data support qualifying the cleaning performance of the PCM, assessing the quantity of scrap generated during the cleaning, and evaluating the impact of fuel retrieval operations on the Basin water quality. The additional data collected primarily consist of weighing fuel and scrap at selected points in the operation, as well as photographing fuel and scrap as it is processed. The time to perform operations is also monitored for comparison with design predictions. Water quality data are collected to establish a baseline to predict the effectiveness of equipment design for control of contamination and visibility during production operation.

【 预 览 】
附件列表
Files Size Format View
804494.pdf 1252KB PDF download
  文献评价指标  
  下载次数:13次 浏览次数:8次