| Cold Vacuum Drying (CVD) Set Point Determination | |
| PHILIPP, B.L. | |
| COGEMA (United States) | |
| 关键词: Safety Engineering; Vacuum Systems; On-Line Measurement Systems; Drying; Spent Fuel Casks; | |
| DOI : 10.2172/801885 RP-ID : SNF-4451, Rev.2 RP-ID : AC06-96RL13200 RP-ID : 801885 |
|
| 美国|英语 | |
| 来源: UNT Digital Library | |
PDF
|
|
【 摘 要 】
The Safety Class Instrumentation and Control (SCIC) system provides active detection and response to process anomalies that, if unmitigated, would result in a safety event. Specifically, actuation of the SCIC system includes two portions. The portion which isolates the MCO and initiates the safety-class helium (SCHe) purge, and the portion which detects and stops excessive heat input to the MCO on high tempered water MCO inlet temperature. For the MCO isolation and purge, the SCIC receives signals from MCO pressure (both positive pressure and vacuum), helium flow rate, bay high temperature switches, seismic trips and time under vacuum trips.