科技报告详细信息
Availability Analysis of the Ventilation Stack CAM Interlock System
YOUNG, J.
Lockheed Martin Hanford Corporation
关键词: Ventilation Systems;    Air Pollution Monitors;    Stacks;    Interlocks;    Safety Analysis;   
DOI  :  10.2172/801135
RP-ID  :  RPP-5453, Rev.0
RP-ID  :  AC27-99RL14047
RP-ID  :  801135
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

Ventilation Stack Continuous Air Monitor (CAM) Interlock System failure modes, failure frequencies and system availability have been evaluated for the RPP. The evaluation concludes that CAM availability is as high as assumed in the safety analysis and that the current routine system surveillance is adequate to maintain this availability. Further, requiring an alarm to actuate upon CAM failure is not necessary to maintain the availability credited in the safety analysis, nor is such an arrangement predicted to significantly improve system availability. However, if CAM failures were only detected by the 92-day functional tests required in the Authorization Basis (AB), CAM availability would be much less than that credited in the safety analysis. Therefore it is recommended that the current surveillance practice of daily simple system checks, 30-day source checks and 92-day functional tests be continued in order to maintain CAM availability.

【 预 览 】
附件列表
Files Size Format View
801135.pdf 1170KB PDF download
  文献评价指标  
  下载次数:7次 浏览次数:11次