Report on HVAC option selections for a relocatable classroom energy and indoor environmental quality field study
Apte, Michael G. ; Delp, Woody W. ; Diamond, Richard C. ; Hodgson, Alfred T. ; Kumar, Satish ; Rainer, Leo I. ; Shendell, Derek G. ; Sullivan, Doug P. ; Fisk, William J.
Lawrence Berkeley National Laboratory
关键词: Heat Pumps;    Evaporative Cooling;    Particulates;    Hvac Systems;    Environmental Quality;   
DOI  :  10.2172/791841
RP-ID  :  LBNL--49026
RP-ID  :  AC03-76SF00098
RP-ID  :  791841
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

It is commonly assumed that efforts to simultaneously develop energy efficient building technologies and to improve indoor environmental quality (IEQ) are unfeasible. The primary reason for this is that IEQ improvements often require additional ventilation that is costly from an energy standpoint. It is currently thought that health and productivity in work and learning environments requires adequate, if not superior, IEQ. Despite common assumptions, opportunities do exist to design building systems that provide improvements in both energy efficiency and IEQ. This report outlines the selection of a heating, ventilation, and air conditioning (HVAC) system to be used in demonstrating such an opportunity in a field study using relocatable school classrooms. Standard classrooms use a common wall mounted heat pump HVAC system. After reviewing alternative systems, a wall-mounting indirect/direct evaporative cooling system with an integral hydronic gas heating is selected. The anticipated advantages of this system include continuous ventilation of 100 percent outside air at or above minimum standards, projected cooling energy reductions of about 70 percent, inexpensive gas heating, improved airborne particle filtration, and reduced peak load electricity use. Potential disadvantages include restricted climate regions and possible increases in indoor relative humidity levels under some conditions.

【 预 览 】
附件列表
Files Size Format View
791841.pdf 4822KB PDF download
  文献评价指标  
  下载次数:5次 浏览次数:47次