Analysis of IECC2003 Chiller Heat Recovery for Service Water Heating Requirement for New York State | |
Winiarski, David W. | |
Pacific Northwest National Laboratory (U.S.) | |
关键词: Heat Recovery; Computerized Simulation; Payback Period; Energy Conservation; 32 Energy Conservation, Consumption, And Utilization; | |
DOI : 10.2172/15020948 RP-ID : PNNL-14836 RP-ID : AC05-76RL01830 RP-ID : 15020948 |
|
美国|英语 | |
来源: UNT Digital Library | |
【 摘 要 】
The state of New York asked the U.S. Department of Energy to evaluate the cost-effectiveness of the requirement for Heat Recovery for Service Water Heating that exists in the 2003 International Energy Conservation Code to determine whether this requirement should be adopted into the New York State Energy Code. A typical hotel application that would trigger this requirement was examined using whole building simulation software to generate baseline annual chiller and service hot water loads, and a spreadsheet was used to examine the energy savings potential for heat recovery using hourly load files from the simulation. An example application meeting the code requirement was developed, and the energy savings, energy cost savings, and first costs for the heat recovery installation were developed. The calculated payback for this application was 6.3 years using 2002 New York state average energy costs. This payback met the minimum requirements for cost effectiveness established for the state of New York for updating the commercial energy conservation code.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
15020948.pdf | 222KB | download |