科技报告详细信息
Modeling the Air Flow in the 3410 Building Filtered Exhaust Stack System
Recknagle, Kurtis P. ; Barnett, J. M. ; Suffield, Sarah R.
Pacific Northwest National Laboratory (U.S.)
关键词: Cfd;    Ansi;    Filtered Exhaust;    Modeling;    3410 Building;   
DOI  :  10.2172/1071988
RP-ID  :  PNNL-22185
RP-ID  :  AC05-76RL01830
RP-ID  :  1071988
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

Additional ventilation capacity has been designed for the 3410 Building filtered exhaust stack system. The updated system will increase the number of fans from two to three and will include ductwork to incorporate the new fan into the existing stack. Stack operations will involve running various two-fan combinations at any given time. The air monitoring system of the existing two-fan stack was previously found to be in compliance with the ANSI/HPS N13.1-1999 standard, however it is not known if the modified (three-fan) system will comply. Subsequently, a full-scale three-dimensional (3-D) computational fluid dynamics (CFD) model of the modified stack system has been created to examine the sampling location for compliance with the standard. The CFD modeling results show good agreement with testing data collected from the existing 3410 Building stack and suggest that velocity uniformity and flow angles will remain well within acceptance criteria when the third fan and associated ductwork is installed. This includes two-fan flow rates up to 31,840 cfm for any of the two-fan combinations. For simulation cases in which tracer gas and particles are introduced in the main duct, the model predicts that both particle and tracer gas coefficients of variance (COVs) may be larger than the acceptable 20 percent criterion of the ANSI/HPS N13.1-1999 standard for each of the two-fan, 31,840 cfm combinations. Simulations in which the tracers are introduced near the fans result in improved, though marginally acceptable, COV values for the tracers. Due to the remaining uncertainty that the stack will qualify with the addition of the third fan and high flow rates, a stationary air blender from Blender Products, Inc. is considered for inclusion in the stack system. A model of the air blender has been developed and incorporated into the CFD model. Simulation results from the CFD model that includes the air blender show striking improvements in tracer gas mixing and tracer particle dispersion. The results of these simulations suggest the air blender should be included in the stack system to ensure qualification of the stack.

【 预 览 】
附件列表
Files Size Format View
1071988.pdf 4567KB PDF download
  文献评价指标  
  下载次数:11次 浏览次数:51次