Economizer Based Data Center Liquid Cooling with Advanced Metal Interfaces | |
Chainer, Timothy | |
IBM | |
关键词: Data Center; 32 Energy Conservation, Consumption, And Utilization Data Center; | |
DOI : 10.2172/1056809 RP-ID : DOE/EE-0002894 RP-ID : EE0002894 RP-ID : 1056809 |
|
美国|英语 | |
来源: UNT Digital Library | |
【 摘 要 】
A new chiller-less data center liquid cooling system utilizing the outside air environment has been shown to achieve up to 90% reduction in cooling energy compared to traditional chiller based data center cooling systems. The system removes heat from Volume servers inside a Sealed Rack and transports the heat using a liquid loop to an Outdoor Heat Exchanger which rejects the heat to the outdoor ambient environment. The servers in the rack are cooled using a hybrid cooling system by removing the majority of the heat generated by the processors and memory by direct thermal conduction using coldplates and the heat generated by the remaining components using forced air convection to an air- to- liquid heat exchanger inside the Sealed Rack. The anticipated benefits of such energy-centric configurations are significant energy savings at the data center level. When compared to a traditional 10 MW data center, which typically uses 25% of its total data center energy consumption for cooling this technology could potentially enable a cost savings of up to $800,000-$2,200,000/year (assuming electricity costs of 4 to 11 cents per kilowatt-hour) through the reduction in electrical energy usage.