科技报告详细信息
Alternative Approaches for Incentivizing the Frequency Responsive Reserve Ancillary Service
Ela, E. ; Milligan, M. ; Kirby, B. ; Tuohy, A. ; Brooks, D.
National Renewable Energy Laboratory (U.S.)
关键词: Electricity Response;    Electricity Demand;    17 Wind Energy;    Stabilization Frequency Response;    24 Power Transmission And Distribution;   
DOI  :  10.2172/1037501
RP-ID  :  NREL/TP-5500-54393
RP-ID  :  AC36-08GO28308
RP-ID  :  1037501
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】
Frequency responsive reserve is the autonomous response of generators and demand response to deviations of system frequency, usually as a result of the instantaneous outage of a large supplier. Frequency responsive reserve arrests the frequency decline resulting in the stabilization of system frequency, and avoids the triggering of under-frequency load-shedding or the reaching of unstable frequencies that could ultimately lead to system blackouts. It is a crucial service required to maintain a reliable and secure power system. Regions with restructured electricity markets have historically had a lack of incentives for frequency responsive reserve because generators inherently provided the response and on large interconnected systems, more than sufficient response has been available. This may not be the case in future systems due to new technologies and declining response. This paper discusses the issues that can occur without proper incentives and even disincentives, and proposes alternatives to introduce incentives for resources to provide frequency responsive reserve to ensure an efficient and reliable power system.
【 预 览 】
附件列表
Files Size Format View
1037501.pdf 527KB PDF download
  文献评价指标  
  下载次数:13次 浏览次数:24次