科技报告详细信息
National Account Energy Alliance Final Report for the Ritz Carlton, San Francisco Combined Heat and Power Project
Rosfjord, Thomas J1 
[1] UTC Power
关键词: CALIFORNIA;    HOTELS;    COGENERATION;    DUAL-PURPOSE POWER PLANTS;    GAS TURBINE POWER PLANTS;    ABSORPTION REFRIGERATION CYCLE;    COMPUTERIZED CONTROL SYSTEMS;    WASTE HEAT UTILIZATION;   
DOI  :  10.2172/932083
RP-ID  :  ORNL/TM-2007/101
PID  :  OSTI ID: 932083
Others  :  TRN: US200813%%308
学科分类:能源(综合)
美国|英语
来源: SciTech Connect
PDF
【 摘 要 】

Under collaboration between DOE and the Gas Technology Institute (GTI), UTC Power partnered with Host Hotels and Resorts to install and operate a PureComfort 240M Cooling, Heating and Power (CHP) System at the Ritz-Carlton, San Francisco. This packaged CHP system integrated four microturbines, a double-effect absorption chiller, two fuel gas boosters, and the control hardware and software to ensure that the system operated predictably, reliably, and safely. The chiller, directly energized by the recycled hot exhaust from the microturbines, could be configured to provide either chilled or hot water. As installed, the system was capable of providing up to 227 kW of net electrical power and 142 RT of chilled water at a 59F ambient temperature.

【 预 览 】
附件列表
Files Size Format View
RO201705190000436LZ 2715KB PDF download