科技报告详细信息
STEADY STATE FLAMMABLE GAS RELEASE RATE CALCULATION AND LOWER FLAMMABILITY LEVEL EVALUATION FOR HANFORD TANK WASTE
MEACHAM JE
关键词: AR FACILITIES;    EVALUATION;    FLAMMABILITY;    VENTILATION;    STORAGE FACILITIES;    RADIOACTIVE WASTES;    DEGASSING;    HANFORD RESERVATION;    LIMITING VALUES;   
DOI  :  10.2172/967371
RP-ID  :  RPP-5926 Rev 9
PID  :  OSTI ID: 967371
Others  :  Other: ECN-721735-R13
Others  :  TRN: US0904523
学科分类:核能源与工程
美国|英语
来源: SciTech Connect
PDF
【 摘 要 】
This report assesses the steady state flammability level under off normal ventilation conditions in the tank headspace for 28 double-shell tanks (DST) and 149 single shell-tanks (SST) at the Hanford Site. Flammability was calculated using estimated gas release rates, Le Chatelier's rule, and lower flammability limits of fuels in an air mixture. This revision updates the hydrogen generation rate input data for all 177 tanks using waste composition information from the Best Basis Inventory Detail Report (data effective as of August 4,2008). Assuming only barometric breathing, the shortest time to reach 25% of the lower flammability limit is 11 days for DSTs (i.e., tank 241-AZ-10l) and 36 days for SSTs (i.e., tank 241-B-203). Assuming zero ventilation, the shortest time to reach 25% of the lower flammability limit is 10 days for DSTs (i.e., tank 241-AZ-101) and 34 days for SSTs (i.e., tank 241-B-203).
【 预 览 】
附件列表
Files Size Format View
RO201705170000566LZ 6155KB PDF download
  文献评价指标  
  下载次数:4次 浏览次数:24次