Infiltration Effects on Residential Pollutant Concentrations for Continuous and Intermittent Mechanical Ventilation Approaches
Sherman, Max ; Logue, Jennifer ; Singer, Brett
关键词: 32;    ACUTE EXPOSURE;    AIR CONDITIONING;    CHRONIC EXPOSURE;    CLIMATES;    ENGINEERS;    HEATING;    INDOORS;    METRICS;    NORTH AMERICA;    PERFORMANCE;    POLLUTANTS;    SIMULATION;    VENTILATION;    VENTILATION SYSTEMS;   
DOI  :  10.2172/991747
RP-ID  :  LBNL-3978E
PID  :  OSTI ID: 991747
Others  :  TRN: US201022%%49
美国|英语
来源: SciTech Connect
PDF
【 摘 要 】

The prevailing residential ventilation standard in North America, American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Standard 62.2, specifies volumetric airflow requirements as a function of the overall size of the home and the number of bedrooms, assumes a fixed, minimal amount of infiltration, and requires mechanical ventilation to achieve the remainder. The standard allows for infiltration credits and intermittent ventilation patterns that can be shown to provide comparable performance. Whole-house ventilation methods have a substantial effect on time-varying indoor pollutant concentrations. If alternatives specified by Standard 62.2, such as intermittent ventilation, are used, short-term pollutant concentrations could exceed acute health standards even if chronic health standards are met.The authors present a methodology for comparing ASHRAE- and non-ASHRAE-specified ventilation scenarios on relative indoor pollutant concentrations. We use numerical modeling to compare the maximum time-averaged concentrations for acute exposure relevant (1-hour, 8-hour, 24-hour ) and chronic exposure relevant (1-year) time periods for four different ventilation scenarios in six climates with a range of normalized leakage values. The results suggest that long-term concentrations are the most important metric for assessing the effectiveness of whole-house ventilation systems in meeting exposure standards and that, if chronic health exposure standards are met, acute standards will also be met.

【 预 览 】
附件列表
Files Size Format View
RO201704240002105LZ 1059KB PDF download
  文献评价指标  
  下载次数:18次 浏览次数:33次