Assessment of the Idaho National Laboratory Hot Fuel Examination Facility Stack Monitoring Site for Compliance with ANSI/HPS N13.1 1999
Glissmeyer, John A. ; Flaherty, Julia E.
关键词: AIR CONDITIONING;    COMPLIANCE;    CROSS SECTIONS;    DUCTS;    HEATING;    HVAC SYSTEMS;    MODIFICATIONS;    MONITORING;    NUCLEAR FACILITIES;    PROBES;    RADIOACTIVE EFFLUENTS;    REGUL;   
DOI  :  10.2172/1010479
RP-ID  :  PNNL-19659
PID  :  OSTI ID: 1010479
Others  :  Other: 830403000
Others  :  TRN: US1101940
美国|英语
来源: SciTech Connect
PDF
【 摘 要 】

This document reports on a series of tests to determine whether the location of the air sampling probe in the Hot Fuels Examination Facility (HFEF) heating, ventilation and air conditioning (HVAC) exhaust duct meets the applicable regulatory criteria regarding the placement of an air sampling probe. Federal regulations require that a sampling probe be located in the exhaust stack according to the criteria of the ANSI/HPS N13.1-1999, Sampling and Monitoring Releases of Airborne Radioactive Substances from the Stacks and Ducts of Nuclear Facilities. These criteria address the capability of the sampling probe to extract a sample that is representative of the effluent stream. The tests conducted by PNNL during July 2010 on the HFEF system are described in this report. The sampling probe location is approximately 20 feet from the base of the stack. The stack base is in the second floor of the HFEF, and has a building ventilation stream (limited potential radioactive effluent) as well as a process stream (potential radioactive effluent, but HEPA-filtered) that feeds into it. The tests conducted on the duct indicate that the process stream is insufficiently mixed with the building ventilation stream. As a result, the air sampling probe location does not meet the criteria of the N13.1-1999 standard. The series of tests consists of various measurements taken over a grid of points in the duct cross section at the proposed sampling-probe location. The results of the test series on the HFEF exhaust duct as it relates to the criteria from ANSI/HPS N13.1-1999 are desribed in this report. Based on these tests, the location of the air sampling probe does not meet the requirements of the ANSI/HPS N13.1-1999 standard, and modifications must be made to either the HVAC system or the air sampling probe for compliance. The recommended approaches are discussed and vary from sampling probe modifications to modifying the junction of the two air exhaust streams.

【 预 览 】
附件列表
Files Size Format View
RO201704240001366LZ 1660KB PDF download
  文献评价指标  
  下载次数:15次 浏览次数:28次