Improved Performance of an Air Cooled Condenser (ACC) Using SPX Wind Guide Technology at Coal-Based Thermoelectric Power Plants
Ken Mortensen
关键词: AIR;    COAL;    CONFIGURATION;    COOLING SYSTEMS;    DESIGN;    EFFICIENCY;    EVALUATION;    FABRICATION;    HEAT TRANSFER;    PERFORMANCE;    PLANNING;    POWER PLANTS;    PROCUREMENT;    SCHEDULES;    TESTING;    VELOCITY;   
DOI  :  10.2172/1025180
RP-ID  :  None
PID  :  OSTI ID: 1025180
Others  :  TRN: US201120%%442
美国|英语
来源: SciTech Connect
PDF
【 摘 要 】

This project added a new airflow enhancement technology to an existing ACC cooling process at a selected coal power plant. Airflow parameters and efficiency improvement for the main plant cooling process using the applied technology were determined and compared with the capabilities of existing systems. The project required significant planning and pre-test execution in order to reach the required Air Cooled Condenser system configuration for evaluation. A host Power Plant ACC system had to be identified, agreement finalized, and addition of the SPX ACC Wind Guide Technology completed on that site. Design of the modification, along with procurement, fabrication, instrumentation, and installation of the new airflow enhancement technology were executed. Baseline and post-modification cooling system data was collected and evaluated. The improvement of ACC thermal performance after SPX wind guide installation was clear. Testing of the improvement indicates there is a 5% improvement in heat transfer coefficient in high wind conditions and 1% improvement at low wind speed. The benefit increased with increasing wind speed. This project was completed on schedule and within budget.

【 预 览 】
附件列表
Files Size Format View
RO201704240000047LZ 7263KB PDF download
  文献评价指标  
  下载次数:30次 浏览次数:43次