Measure Guideline: Condensing Boilers - Optimizing Efficiency and Response Time During Setback Operation
Arena, L.
关键词: RESIDENTIAL;    RESIDENTIAL BUILDINGS;    CARB II;    BUILDING AMERICA;    GAS-FIRED;    MODULATING CONDENSING BOILERS;    OUTDOOR RESET CONTROL;    NIGHT SETBACK;    AFUE;    RIGHT-SIZING;    HYDRONIC SYSTEMS;    MASS STORAGE;    ACCA MANUAL J;    BOOST CONTROL;    BASEBOARD CONVECTORS;    INDIRECT DHW SYSTEM;    COMBUSTION EFFICIENCY;    RECOVERY PERIOD;    Buildings;   
DOI  :  10.2172/1126299
RP-ID  :  DOE/GO-102014-4369
PID  :  OSTI ID: 1126299
Others  :  Other: KNDJ-0-40342-03
学科分类:能源(综合)
美国|英语
来源: SciTech Connect
PDF
【 摘 要 】

Conventional wisdom surrounding space heating has told us a couple of things consistently for several years now: size the mechanical systems to the heating loads and setting the thermostat back at night will result in energy savings. The problem is these two recommendations oppose each other. A system that is properly sized to the heating load will not have the extra capacity necessary to recover from a thermostat setback, especially at design conditions. The implication of this is that, for setback to be successfully implemented, the heating system must be oversized. This issue is exacerbated further when an outdoor reset control is used with a condensing boiler, because not only is the system matched to the load at design, the outdoor reset control matches the output to the load under varying outdoor temperatures. Under these circumstances, the home may never recover from setback. Special controls to bypass the outdoor reset sensor are then needed. Properly designing a hydronic system for setback operation can be accomplished but depends on several factors. Determining the appropriateness of setback for a particular project is the first step. This is followed by proper sizing of the boiler and baseboard to ensure the needed capacity can be met. Finally, control settings must be chosen that result in the most efficient and responsive performance. This guide provides step by step instructions for heating contractors and hydronic designers for selecting the proper control settings to maximize system performance and improve response time when using a thermostat setback.

【 预 览 】
附件列表
Files Size Format View
1396KB PDF download
  文献评价指标  
  下载次数:9次 浏览次数:17次