科技报告详细信息
Analysis of Loss-of-Offsite-Power Events 1998???2013
Schroeder, John Alton1 
[1]Idaho National Lab. (INL), Idaho Falls, ID (United States). Risk Assessment and Management Services Dept.
关键词: duration;    frequency;    loss of offsite power;    operating experience;   
DOI  :  10.2172/1261724
RP-ID  :  INL/EXT--15-34443
PID  :  OSTI ID: 1261724
学科分类:能源(综合)
美国|英语
来源: SciTech Connect
PDF
【 摘 要 】
Loss of offsite power (LOOP) can have a major negative impact on a power plant???s ability to achieve and maintain safe shutdown conditions. Risk analyses suggest that loss of all alternating current power contributes over 70% of the overall risk at some U.S. nuclear plants. LOOP event and subsequent restoration of offsite power are important inputs to plant probabilistic risk assessments. This report presents a statistical and engineering analysis of LOOP frequencies and durations at U.S. commercial nuclear power plants. The data used in this study are based on the operating experience during calendar years 1997 through 2013. Frequencies and durations were determined for four event categories: plant-centered, switchyard-centered, grid-related, and weather-related. The emergency diesel generator failure modes considered are failure to start, failure to load and run, and failure to run more than 1 hour. The component reliability estimates and the reliability data are trended for the most recent 10-year period while yearly estimates for reliability are provided for the entire active period. No statistically significant trends in LOOP frequencies over the 1997???2013 period are identified. There is a possibility that a significant trend in grid-related LOOP frequency exists that is not easily detected by a simple analysis. Statistically significant increases in recovery times after grid- and switchyard-related LOOPs are identified.
【 预 览 】
附件列表
Files Size Format View
1465KB PDF download
  文献评价指标  
  下载次数:13次 浏览次数:39次