Smoke toxicity of rainscreen facades
Article
Peck, Gabrielle1  Jones, Nicola1  McKenna, Sean T.1  Glockling, Jim L. D.2  Harbottle, John2  Stec, Anna A.1  Hull, T. Richard1 
[1] Univ Cent Lancashire, Ctr Fire & Hazard Sci, Preston PR1 2HE, Lancs, England
[2] Fire Protect Assoc, London Rd, Moreton Marsh GL56 0RH, Glos, England
关键词: Incapacitation;    lethality;    carbon monoxide;    CO;    hydrogen cyanide;    HCN;    polyisocyanurate;    PIR;    phenolic;    stone wool;    fire;    combustion;   
DOI  :  10.1016/j.jhazmat.2020.123694
来源: Elsevier
PDF
【 摘 要 】

The toxic smoke production of four rainscreen facade systems were compared during large-scale fire performance testing on a reduced height BS 8414 test wall. Systems comprising Mon-combustible' aluminium composite material (ACM) with polyisocyanurate (PIR), phenolic foam (PF) and stone wool (SW) insulation, and polyethylene-filled ACM with PIR insulation were tested. Smoke toxicity was measured by sampling gases at two points - the exhaust duct of the main test room and an additional 'kitchen vent', which connects the rainscreen cavity to an occupied area. Although the toxicity of the smoke was similar for the three insulation products with non-combustible ACM, the toxicity of the smoke flowing from the burning cavity through the kitchen vent was greater by factors of 40 and 17 for PIR and PF insulation respectively, when compared to SW. Occupants sheltering in a room connected to the vent are predicted to collapse, and then inhale a lethal concentration of asphyxiant gases. This is the first report quantifying fire conditions within the cavity and assessing smoke toxicity within a rainscreen facade cavity.

【 授权许可】

Free   

【 预 览 】
附件列表
Files Size Format View
10_1016_j_jhazmat_2020_123694.pdf 5230KB PDF download
  文献评价指标  
  下载次数:4次 浏览次数:0次