期刊论文详细信息
RENEWABLE ENERGY 卷:96
Heat recovery from air in underground transport tunnels
Article
Ninikas, Konstantinos1  Hytiris, Nicholas1  Emmanuel, Rohinton1  Aaen, Bjorn1  Younger, Paul L.2 
[1] Glasgow Caledonian Univ, Sch Engn & Built Environm, Glasgow G4 0BA, Lanark, Scotland
[2] Univ Glasgow, Sch Engn, Glasgow G12 8QQ, Lanark, Scotland
关键词: Heat recovery;    Thermal comfort;    Air source heat pump;   
DOI  :  10.1016/j.renene.2016.05.015
来源: Elsevier
PDF
【 摘 要 】

The performance of a typical air source heat pump could be increased dramatically by a relatively stable air temperature with a high humidity, even during the peak heating months. In this short communication we show such conditions exist in the underground transport tunnels of the Glasgow Subway system, where we had conducted an annual survey of air flow, air temperature and relative humidity at thirty different points within the subway network. We found relatively stable temperatures and sufficient air movement inside the twin tunnels (average temperature during winter = 15 degrees C, annual variation = 2.6 degrees C; average air flow = 16.47 m(3)/h) indicating higher system efficiency compared to a conventional air source heat pump installation. Potential energy and carbon savings are discussed. (C) 2016 Elsevier Ltd. All rights reserved.

【 授权许可】

Free   

【 预 览 】
附件列表
Files Size Format View
10_1016_j_renene_2016_05_015.pdf 1851KB PDF download
  文献评价指标  