期刊论文详细信息
RENEWABLE ENERGY 卷:36
Impact of active power curtailment on overvoltage prevention and energy production of PV inverters connected to low voltage residential feeders
Article
Tonkoski, Reinaldo1  Lopes, Luiz A. C.1 
[1] Concordia Univ, Montreal, PQ H3G 1M8, Canada
关键词: Power distribution;    Overvoltages;    Solar power generation;    Power systems;    Power quality;    Voltage control;   
DOI  :  10.1016/j.renene.2011.05.031
来源: Elsevier
PDF
【 摘 要 】

As non-controllable power sources, photovoltaics (PV) can create overvoltage in low voltage (LV) distribution feeders during periods of high generation and low load. This is usually prevented passively by limiting the penetration level of PV to very conservative values, even if the critical periods rarely occur. Alternatively, one can use active power curtailment (APC) techniques, reducing the amount of active power injected by the PV inverters, as the voltage at their buses increase above a certain value. In this way, it is possible to increase the installed PV capacity and energy yield while preventing overvoltage. This paper investigates a number of approaches for sizing and controlling the PV power generated by 12 net-zero energy houses equipped with large rooftop PV systems in a typical 240 V/75 kVA Canadian suburban radial distribution feeder. Simulations of a one year period with typical solar irradiance and load profiles are conducted with PSCAD to assess the performance of the different approaches in terms of overvoltage occurrence, sharing of the burden for overvoltage prevention per house and total energy yield of the residential PV feeder. (C) 2011 Elsevier Ltd. All rights reserved.

【 授权许可】

Free   

【 预 览 】
附件列表
Files Size Format View
10_1016_j_renene_2011_05_031.pdf 958KB PDF download
  文献评价指标  
  下载次数:8次 浏览次数:1次