期刊论文详细信息
RENEWABLE ENERGY 卷:118
Performance assessment of a photonic radiative cooling system for office buildings
Article
Wang, Weimin1  Fernandez, Nick2  Katipamula, Srinivas2  Alvine, Kyle2 
[1] Univ North Carolina Charlotte, Dept Engn Technol, Charlotte, NC 28223 USA
[2] Pacific Northwest Natl Lab, Richland, WA 99352 USA
关键词: Radiative cooling;    Radiant cooling;    Energy simulation;    Photonic material;    Building performance;   
DOI  :  10.1016/j.renene.2017.10.062
来源: Elsevier
PDF
【 摘 要 】

Recent advances in materials have demonstrated the ability to maintain radiator surfaces at below ambient temperatures in the presence of intense, direct sunlight. Daytime radiative cooling is promisifig for building applications. This paper estimates the energy savings from daytime radiative cooling, specifically based on photonic materials. A photonic radiative cooling system was proposed and modeled using the whole energy simulation program EnergyPlus. A typical medium-sized office building was used for the simulation analysis. Several reference systems were established to quantify the potential of energy savings from the photonic radiative cooling system. The reference systems include a variable-air volume (VAV) system, a hydronic radiant system, and a nighttime radiative cooling system. The savings analysis was made for a number of locations with different climates. Simulation results showed that the photonic radiative cooling system saved between 45% and 68% cooling electricity relative to the VAV system and between 9% and 23% relative to the nighttime radiative cooling system featured with the best coating commercially available on market. A simple economic analysis was also made to estimate the maximum acceptable incremental cost for upgrading from nighttime cooling to photonic radiative cooling. (C) 2017 Elsevier Ltd. All rights reserved.

【 授权许可】

Free   

【 预 览 】
附件列表
Files Size Format View
10_1016_j_renene_2017_10_062.pdf 607KB PDF download
  文献评价指标  
  下载次数:12次 浏览次数:1次