期刊论文详细信息
Machines
Voltage Profile Enhancement and Loss Minimization Using Optimal Placement and Sizing of Distributed Generation in Reconfigured Network
GerardoOndo Micha Adjayeng1  Waseem Haider1  Chul-Hwan Kim1  SJarjees Ul Hassan1  Arif Hussain1  Arif Mehdi1 
[1] Department of Electrical and Computer Engineering, Sungkyunkwan University, Suwon 16419, Korea;
关键词: distributed generation;    voltage deviation;    power loss minimization;    particle swarm optimization;    network reconfiguration;    voltage stability enhancement;   
DOI  :  10.3390/machines9010020
来源: DOAJ
【 摘 要 】

Power loss and voltage instability are major problems in distribution systems. However, these problems are typically mitigated by efficient network reconfiguration, including the integration of distributed generation (DG) units in the distribution network. In this regard, the optimal placement and sizing of DGs are crucial. Otherwise, the network performance will be degraded. This study is conducted to optimally locate and sizing of DGs into a radial distribution network before and after reconfiguration. A multi-objective particle swarm optimization algorithm is utilized to determine the optimal placement and sizing of the DGs before and after reconfiguration of the radial network. An optimal network configuration with DG coordination in an active distribution network overcomes power losses, uplifts voltage profiles, and improves the system stability, reliability, and efficiency. For considering the actual power system scenarios, a penalty factor is also considered, this penalty factor plays a crucial role in the minimization of total power loss and voltage profile enhancement. The simulation results showed a significant improvement in the percentage power loss reduction (32% and 68.05% before and after reconfiguration, respectively) with the inclusion of DG units in the test system. Similarly, the minimum bus voltage of the system is improved by 4.9% and 6.53% before and after reconfiguration, respectively. The comparative study is performed, and the results showed the effectiveness of the proposed method in reducing the voltage deviation and power loss of the distribution system. The proposed algorithm is evaluated on the IEEE-33 bus radial distribution system, using MATLAB software.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次