Труды Крыловского государственного научного центра | |
Short-circuit currents versus inductive reactances of turbo-genset for different types of shorts | |
Beligma S. Dorzhieva1  | |
[1] JSC Power Machines, St. Petersburg, Russia; | |
关键词: turbo-genset; short circuit; subtransient reactance; transient reactance; short-circuit current; | |
DOI : 10.24937/2542-2324-2021-2-S-I-60-65 | |
来源: DOAJ |
【 摘 要 】
This paper discusses how short-circuit currents of turbo-genset depend on its inductive reactances for the cases of triple-, double- and single-phase shorts. The study tackles air-cooled turbo-gensets. The purpose of this work was to investigate the effect of changes in synchronous, transient and subtransient inductive reactances of turbo-genset upon short-circuit currents for different types of shorts. Short-circuit currents were calculated as per Park-Gorev equations. The changes in currents were plotted against both longitudinal and transverse axes. The results were further used to plot short-circuit currents as functions of subtransient and transient turbo-genset reactances. These plots show that even a minor change in subtransient and transient reactance results in a significant change of short-circuit current.