期刊论文详细信息
The Journal of Engineering
Calculation and control of DC bias current distribution in an AC power system around a typical ±800 kV DC grounding electrode
Wanlin Quan1  Shifeng Yu2  Fangjie Wu2  Zheng Zhao2 
[1] School of Electrical Engineering, Wuhan University;State Grid Economic and Technological Research Institute Co., Ltd.;
关键词: earthing;    power transformers;    current distribution;    DC transformers;    HVDC power transmission;    earth electrodes;    HVDC power convertors;    power transmission control;    power capacitors;    resistors;    voltage 800.0 kV;    neutral earthed transformers;    CDEGS;    resistor limiting method;    blocking capacitor;    Shanghaimiao-to-Shandong UHVDC Transmission Project;    DC current flows;    UHVDC transmission system;    DC bias current distribution control;    converter station;    monopolar ground return mode;    ultra-high-voltage direct current transmission system;    DC grounding electrode;    AC power system;    UHVDC grounding electrode;    DC bias problem;    DC potential;    DC bias calculation model;   
DOI  :  10.1049/joe.2018.8509
来源: DOAJ
【 摘 要 】

When the ultra-high-voltage direct current (UHVDC) transmission system operates in a monopolar ground return mode, an enormous DC current flows into earth via the DC grounding electrode in the converter station and then comes into the AC system around the converter station through the neutral earthed transformers, which will cause DC bias in AC systems and harm the transformers' safe operation. In this study, the DC current distribution in the AC systems around the Linyi converter station of the Shanghaimiao-to-Shandong UHVDC Transmission Project was studied. Based on the direct field-circuit coupled method, the DC bias calculation model was established in CDEGS. By using the model, the DC potential in the earth and the DC current distribution in the AC systems were calculated. Then, the DC current distribution in the AC systems was calculated and analysed after adopting a blocking capacitor and a resistor limiting method in a comprehensive way, and the effect of this controlling method was evaluated further. The research results have some practical engineering guiding significance for solving the DC bias problem of AC systems around the UHVDC grounding electrode.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次