期刊论文详细信息
Energies
The Half-Sine Method: A New Accurate Location Method Based on Wavelet Transform for Transmission-Line Protection from Single-Ended Measurements
Miguel García-Gracia1  Susana Martín Arroyo1  Antonio Montañés1 
[1] Dpto. Ingeniería Eléctrica, Universidad de Zaragoza, 50018 Zaragoza, Spain;
关键词: fault location;    discrete wavelet transform;    traveling waves;    fault detection;    transmission-line protection;   
DOI  :  10.3390/en12173293
来源: DOAJ
【 摘 要 】

In this work, a new and accurate method based on the wavelet transform is proposed for fault location in transmission-line systems. The proposed wavelet method consists of the analysis of the transient signal measured at a single end of the transmission line. Aerial current modes are used, and zero modes are included in the fault-detection scheme for low fault-inception angles. The fault distance is evaluated using the wavelet modulus maxima technique and a method based on the response to a half-sine voltage is proposed to overcome drawbacks arising from the limited sampling frequency and low fault-inception angle. The fault distance is calculated using the difference between the time when a 100 kHz half-sine signal is sent and the time when the derivative signal is received. The proposed algorithm is tested considering harmonic distortion and varying fault resistance, ground resistivity, location and inception angle. The high accuracy of the proposed algorithm is obtained even for faults close to the bus and low inception angles.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次