Journal of Modern Power Systems and Clean Energy | |
Phase Angle Control Based Three-phase DVR with Power Factor Correction at Point of Common Coupling | |
Hoay Beng Gooi1  Jian Ye1  | |
[1] Nanyang Technological University,Singapore,639798; | |
关键词: Dynamic voltage restorer (DVR); voltage sag and swell compensation; phase angle control (PAC) method; power factor correction; | |
DOI : 10.35833/MPCE.2018.000428 | |
来源: DOAJ |
【 摘 要 】
This paper investigates the ability of correcting the power factor at the point of common coupling (PCC) of the source side using dynamic voltage restorer (DVR). By applying the phase angle control (PAC) method, the DVR compensating voltage will be injected with a specific phase angle and magnitude in series with the transmission line, which leads to a power factor angle shift of the resultant load voltage. As a result, the source voltage is always in phase with the source current under different load conditions, which means that the power factor correction is achieved at the PCC of the source side. A laboratorial prototype of the DVR is utilized to verify the proposed control algorithm. The experimental results validate that an approximate unity power factor can be maintained at the source side.
【 授权许可】
Unknown