Case Studies for Non-Detection of Islanding by Grid-Connected In-Parallel Photovoltaic and Electrical Energy Storage Systems Inverters
HyeMi Hwang1  YoungSeok Jung1  Hyung-Jun Song1  JongRok Lim1  Young-Chul Ju1  GiHwan Kang1  WooGyun Shin1  SukWhan Ko1 
[1] Photovoltaics Laboratory, New and Renewable Energy Institute, Korea Institute of Energy Research, Daejeon 34129, Korea;
关键词: anti-islanding;    anti-islanding detect;    EESS inverter;    PV inverter;    PV system;   
DOI  :  10.3390/app9050817
来源: DOAJ
【 摘 要 】

In Korea, there is a rule for Renewable Energy Certification with weighting 5.0, to expand grid linkage capacity and to improve the stability of the grid to accommodate photovoltaic (PV) systems in a distributed power system. Due to this rule, many power companies and operators are trying to install electrical energy storage systems that are able to operate in conjunction with PV system power. These systems operate in parallel at the same grid connection point. This paper presents the results of case studies on the failure to detect islanding operation. Test evaluation devices that could be bi-directionally charged and discharged were implemented for an islanding detection test. Testing was conducted under a variety of operating conditions. When a single inverter was operated under the islanding condition, it was stably stopped within 0.5 s using the Korean grid-code standard. However, when two inverters were operated at the same time under the islanding condition, islanding detection failed and the two inverters continued to feed the connected RLC (resistor, inductor, capacitor) loads in the isolated section known as an island. Different algorithms used by PCS (power conversion system) manufacturers to detect islanding might cause this phenomenon. Therefore, it is necessary for a new PCS test standard to detect islanding.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次