期刊论文详细信息
Energy Reports
Power swing detecting method using principal components analysis
Feng Liu1  Yuanyuan Dai2  Xinzhou Dong3  Jianli Hu3  Xiaoning Kang3  Hao Wang4  Wenzhong Li4  Luchuan Fu4 
[1] Corresponding author.;Xi’an Jiaotong University, Beilin District, Xi’an, 710049, China;Shaanxi Electric Power Company, Beilin District, Xi’an, 710048, China;Tsinghua University, Haidian District, Beijing, 100084, China;
关键词: Distance protection;    AC transmission system;    Power swing;    Principal components analysis;    Power swing detecting;   
DOI  :  
来源: DOAJ
【 摘 要 】

During power swing, the distance protection is easily affected by the oscillations of voltage and current which may lead to the mal-operation of the protection. Therefore, a power swing detecting unit is needed to cooperate with distance protection. In this paper, a power swing detecting method based on the difference between the structure of transmission line under fault situations and that under power swing situations is proposed. Principal component analysis is deployed to process the voltage and current data to extract the structure feature of the transmission line under power swing and fault situations. To test the effectiveness of the proposed method, a simulation system is built in PSCAD/EMTDC and different disturbance scenarios are done. The test results indicate that the proposed method can reliably distinguish between power swing and fault situations. Besides, a comparison between the proposed method and methods mentioned in other works is been done. The comparison results show that the proposed method has an advantage in operating speed and is less affected by measuring noise.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:2次