Monitoring of Energy Data with Seamless Temporal Accuracy Based on the Time-Sensitive Networking Standard and Enhanced µPMUs
Miguel González-Redondo1  Víctor Pallarés-López1  Isabel Santiago1  Isabel Moreno-García1  Rafael Jesús Real-Calvo1  Silvia del Rio Jiménez1 
[1] Departamento de Ingeniería Electrónica y de Computadores, Campus de Rabanales, Universidad de Córdoba, 14071 Córdoba, Spain;
关键词: distributed synchronism;    TSN;    gPTP;    microgrid;    µPMU;    synthetic models;   
DOI  :  10.3390/app11199126
来源: DOAJ
【 摘 要 】

In the energy sector, distributed synchronism and a high degree of stability are necessary for all real-time monitoring and control systems. Instantaneous response to critical situations is essential for the integration of renewable energies. The most widely used standards for clock synchronisation, such as Network Time Protocol (NTP) and Precision Time Protocol (PTP), do not allow for achieving synchronised simultaneous sampling in distributed systems. In this work, a novel distributed synchronism system based on the Time-Sensitive Networking (TSN) standard has been validated for its integration in an architecture oriented towards the high-resolution digitisation of photovoltaic (PV) generation systems. This method guarantees a time stamping with an optimal resolution that allows for the analysis of the influence of fast-evolving atmospheric fluctuations in several plants located in the same geographical area. This paper proposes an enhanced micro-phasor measurement unit (µPMU) that acts as a phasor meter and TSN master controlling the monitoring system synchronism. With this technique, the synchronism would be extended to the remaining measurement systems that would be involved in the installation at distances greater than 100 m. Several analyses were carried out with an on-line topology of four acquisition systems capturing simultaneously. The influence of the Ethernet network and the transducers involved in the acquisition process were studied. Tests were performed with Ethernet cable lengths of 2, 10, 50, and 75 m. The results were validated with 24-bit Sigma-Delta converters and high-precision resistor networks specialised in high-voltage monitoring. It was observed that with an appropriate choice of sensors and TSN synchronism, phase errors of less than ±1 µs can be guaranteed by performing distributed captures up to 50 kS/s. Statistical analysis showed that uncertainties of less than ±100 ns were achieved with 16-bit Successive Approximation Register (SAR) converters at a moderate cost. Finally, the requirements of the IEEE C37.118.1-2011 standard for phasor measurement units (PMU) were also satisfied. This standard establishes an uncertainty of ±3.1 μs for 50 Hz systems. These results demonstrate the feasibility of implementing a simultaneous sampling system for distributed acquisition systems coordinated by a µPMU.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次