期刊论文详细信息
Energies
Impact of Weather Conditions on the Operation of Power Unit Cooling Towers 905 MWe
Katarzyna Widera1  Janusz Pospolita2  Anna Kuczuk2  Zbigniew Buryn3  Rafał Smejda4 
[1] Faculty of Economics and Management, Opole University of Technology, Prószkowska 76, 45-758 Opole, Poland;Faculty of Mechanical Engineering, Opole University of Technology, Prószkowska 76, 45-758 Opole, Poland;Faculty of Production Engineering and Logistics, Opole University of Technology, Prószkowska 76, 45-758 Opole, Poland;PGE GIK S.A. Branch Opole Power Plant, Brzezie k., 46-021 Opola, Poland;
关键词: cooling tower;    ambient conditions;    water loss;    power plant;   
DOI  :  10.3390/en14196412
来源: DOAJ
【 摘 要 】

The paper presents the results of measurements and calculations concerning the influence of weather conditions on the operation of wet cooling towers of 905 MWe units of the Opole Power Plant (Poland). The research concerned the influence of temperature and relative humidity of air, wind and power unit load on the water temperature at the outlet from the cooling tower, the level of water cooling, cooling efficiency and cooling water losses. In the cooling water loss, the evaporation loss stream and the drift loss stream were distinguished. In the analyzed operating conditions of the power unit, for example, an increase in Tamb air by 5 °C (from 2022 °C to 2527 °C) causes an increase in temperature at the outlet of the cooling tower by 34 °C. The influence of air temperature and humidity on the level of water cooling ΔTw and cooling efficiency ε were also found. In the case of ΔTw, the effect is in the order of 0.10.2 °C and results from the change in cooling water temperature and the heat exchange in the condenser. The ε value is influenced by air temperature and humidity, which determine the wet bulb temperature value. Within the range of power changes of the unit from 400 to 900 MWe, the evaporated water stream m˙ev, depending on the environmental conditions, increases from 400600 tons/h to the value of 10001400 tons/h. It was determined that in the case of the average power of the unit at the level of 576.6 MWe, the average values of the evaporation and drift streams were respectively 0.78% and 0.15% of the cooling water stream. Using statistical methods, it was found that the influence of wind on the level of water cooling, cooling efficiency and cooling water losses was statistically significant.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次