| Energies | |
| Effect of Tower Shadow and Wind Shear in a Wind Farm on AC Tie-Line Power Oscillations of Interconnected Power Systems | |
| Zhe Chen1  Weihao Hu1  Xiaoru Wang2  Jin Tan2  | |
| [1] Department of Energy Technology, Aalborg University, Pontoppidanstraede 101,Aalborg DK-9220, Denmark;School of Electrical Engineering, Southwest Jiaotong University, Chengdu 610031, China; | |
| 关键词: wind power integration; interconnected power systems; tie-line power oscillations; forced power oscillation; low frequency oscillations; tower shadow and wind shear (TSWS); | |
| DOI : 10.3390/en6126352 | |
| 来源: DOAJ | |
【 摘 要 】
This paper describes a frequency domain approach for evaluating the impact of tower shadow and wind shear effects (TSWS) on tie-line power oscillations. A simplified frequency domain model of an interconnected power system with a wind farm is developed. The transfer function, which relates the tie-line power variation to the mechanical power variation of a wind turbine, and the expression of the maximum magnitude of tie-line power oscillations are derived to identify the resonant condition and evaluate the potential risk.The effects of the parameters on the resonant magnitude of the tie-line power are also discussed. The frequency domain analysis reveals that TSWS can excite large tie-line power oscillations if the frequency of TSWS approaches the tie-line resonant frequency, especially in the case that the wind farm is integrated into a relatively small grid and the tie-line of the interconnected system is weak. Furthermore, the results of the theoretical analysis are validated through time domain simulations conducted in the two-area four-generator system and the Western Electric Coordinating Council 127 bus system.
【 授权许可】
Unknown