期刊论文详细信息
Entropy
Exergy Analysis of Fluidized Desiccant Cooling System
Piotr Kolasiński1  Zbigniew Rogala1 
[1] Department of Thermodynamics, Theory of Machines and Thermal Systems, Wrocław University of Science and Technology, Wybrzeże Wyspianskiego 27, 50-370 Wrocław, Poland;
关键词: fluidized bed;    desiccant cooling;    adsorption;    exergy destruction;    exergy efficiency;   
DOI  :  10.3390/e21080757
来源: DOAJ
【 摘 要 】

One of the main challenges in the design and implementation of fluidized desiccant cooling (FDC) systems is increasing their low COP (coefficient of performance). Exergy analysis is one of the tools especially suitable for improvement and optimization of FDC systems. The improvement of performance is impossible as long as the main sources of exergy destruction are not identified and evaluated. In this paper, the exergy analysis was applied in order to identify these components and processes of the FDC system that are mainly responsible for exergy destruction. Moreover, the exergy efficiency of a simple fluidized desiccant cooler was determined. The results showed that fluidized beds and regenerative heat exchanger were the main exergy destruction sources with a 32% and 18% share of total exergy destruction, respectively. On the other hand, the direct evaporative cooler and air cooler placed after the desorbing fluidized bed were characterized by the lowest exergy efficiencies. This work contributes to better understanding of FDC operation principles and improvement of the performance of FDC technology.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次