期刊论文详细信息
Energies
Energy-Saving Strategies of Axial Flow Fans for Direct Dry Cooling System
Lei Chen1  Xiaoze Du1  Lijun Yang1  Wenhui Huang1 
[1] Key Laboratory of Power Station Energy Transfer Conversion and System, Ministry of Education, Beijing 102206, China;
关键词: direct dry cooling system;    air-cooled condenser;    heat exchanger;    energy-saving;    axial flow fan;    power consumption;   
DOI  :  10.3390/en14113176
来源: DOAJ
【 摘 要 】

The operating conditions of axial flow fans are closely related to the thermo-flow characteristics of the mechanical draft direct dry cooling system. Moreover, the uneven distribution of cooling air driven by axial flow fans may lead to the deterioration of the heat transfer capacity of air-cooled condensers (ACCs). Therefore, developing energy-saving operating methods for axial flow fans is very meaningful. In this work, two kinds of adjustment strategies to make the flow field more uniform are proposed for a 2 × 300 MW direct dry cooling power-generating unit. The performance of ACCs in the prevailing wind direction is predicted with the help of the macro heat exchanger model. It is found that the inlet air temperatures of fans are significantly reduced by proposed strategies, especially at high wind speeds. Moreover, the minimum cooling air can meet the cooling demand of ACCs for the strategy which made the air flow rates of all fans consistent. Compared with the case without adjustment of fans, the total power consumption of the fan array was cut down effectively, up to 13.94% at the wind speed of 12 m/s. In conclusion, the energy efficiency of ACCs can be improved by the uniform flow field.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:2次