期刊论文详细信息
Symmetry
Experimental Investigation on the Cooling and Inerting Effects of Liquid Nitrogen Injected into a Confined Space
Wuyi Cheng1  Huaijun Ji1  Yunzhuo Li1  Hetao Su1  Xiang Wu1 
[1] School of Engineering and Technology, China University of Geosciences (Beijing), Beijing 100083, China;
关键词: liquid nitrogen;    confined space;    heat transfer;    cooling rate;    inerting coefficient;   
DOI  :  10.3390/sym11040579
来源: DOAJ
【 摘 要 】

As a highly effective and environmentally benign suppression agent, liquid nitrogen (LN2) has been widely used for fire extinguishing in plants, dwellings, enclosed underground tunnels, and other confined spaces through cooling and inerting. It is of great significance to understand the cooling and inerting effects of LN2 injected into a confined space. A confined-space experimental platform was developed to study the injecting LN2 into the platform with different injection parameters, such as mass flux, pipe diameter, and inclination angle. In addition, a mathematical model of quantitatively assessing cooling and inerting effects was proposed by using heat transfer capacity, inerting coefficient, and cooling rate. Results showed that the inerting effect was gradually enhanced with a mass flux increasing from 0.014 to 0.026 kg/s and then tended to level off; an appropriate pipe diameter of 12 mm was optimal for the cooling and inerting effects in this experiment. In addition, a positively increasing inclination angle could contribute to the cooling and inerting effects. However, there was little effect on the cooling and inerting with an inclination angle less than 0°. This study can provide technical guidances for environmentally friendly fire extinguishing with LN2 in a confined space.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次