期刊论文详细信息
Energies 卷:13
Lessons to Learn from Post-Installation Pollution Levels Assessment of Some Distribution Insulators
JanvierSylvestre N’cho1  Amidou Betie1  KoubaMarie Lucia Yapi2  Fethi Meghnefi2  Epiphane Hounton2  Issouf Fofana2 
[1] Département Génie Électrique et Électronique, Institut National Polytechnique Houphouët Boigny (INP-HB), Yamoussoukro BP 1093, Cote D’Ivoire;
[2] Research Chair on the Aging of Power Network Infrastructure (ViAHT), Université du Québec à Chicoutimi, 555 Boulevard de l’Université, Chicoutimi, QC G7H 2B1, Canada;
关键词: insulator;    pollution;    humidity;    equivalent salt deposit density (ESDD);    non-soluble deposit density (NSDD);    leakage current;   
DOI  :  10.3390/en13164064
来源: DOAJ
【 摘 要 】

Among the main causes of outdoor insulation failures is their poor specifications in terms of leakage distances. This happens when the selected criteria are unable to cope with all the stresses imposed by the changes in environmental pollutions. Therefore, it is important for utilities to fully understand the actual pollution characteristics of the service environment in which the insulators are operating. In this paper, the pollution severity and performance of some 13.2 kV ceramic insulators, sampled in different areas of a Canadian aluminum factory, are assessed. The investigations were performed taking into account the influence of air humidity. Various characteristics were investigated to assess the pollution levels of the insulators, such as equivalent salt deposit density (ESDD) and non-soluble deposit density (NSDD), surface resistance, and leakage current characteristics (density, 3rd harmonic amplitude, and phase). It was witnessed that the insulators, collected around the factory, were much more polluted in comparison to the initial expectation. The pollution level should not be considered static due to the environmental parameters’ dynamics. Lessons to learn: the reliability of an electrical grid is dependent on components whose own reliability is strongly affected by external factors, of which there is often a poor awareness. If care is not taken to re-evaluate the post-installation pollution levels of the insulators, the light may simply turn out!

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次