Thermodynamic optimization of a rack-level water-cooling infrastructure in high load data centers based on the principle of minimum exergy destruction
Jialiang Yang1  Hao Tian1  Hong Zheng2 
[1] Institute of Optics, Fine Mechanics and Physics, Chinese Academy of Sciences, Changchun, Jilin, 130033, China;
[2] School of Aerospace Engineering, Tsinghua University, Beijing, 100083, China;
关键词: Server;    Data center;    Heat transfer;    Exergy;    Optimization;    Case study;   
DOI  :  
来源: DOAJ
【 摘 要 】

Exergy model and the least exergy loss principle are introduced to analyze the exergy loss distribution in heat transfer and air/water flow process, for a combined server/cabinet cooling network. Based on the optimized case suggested by the exergy model, a multi-stage water cooling scheme is designed, with two-stage heat exchanger in server cabinet, and double-chiller in the water loop. Both thermal and energy performance of such cooling infrastructure has been tested in a data center in China, with the measured performance in good agreement with the designed values, and the exergy loss model has been validated.