期刊论文详细信息
Journal of control, automation and electrical systems
An Algorithm for Optimal Placement of Voltage Sag Monitors
article
Junqueira, Caio Marco dos Santos1  Brito, Núbia Silva Dantas1  de Souza, Benemar Alencar1  Coelho, Rodrigo de Almeida1  Lima, Érica Mangueira1 
[1] Power Systems Laboratory (LSP), Department of Electric Engineering (DEE), Federal University of Campina Grande (UFCG)
关键词: Power quality;    Voltage sags;    Observability;    Binary particle swarm optimization;    Sensitivity analysis;   
DOI  :  10.1007/s40313-019-00443-4
学科分类:自动化工程
来源: Springer
PDF
【 摘 要 】

Voltage sags are disturbances that deserve special attention in power quality (PQ) area, given its frequent occurrences. Their constant monitoring is, therefore, essential to diagnose its causes and mitigate economic losses of electric utility customers. However, the cost of a monitoring system may be excessive if not evaluated strategically. In this context, this work presents an algorithm for the installation of PQ monitors at strategic points of electric power distribution systems in order to diagnose voltage sags. Observability area concept and binary particle swarm optimization method were used to evaluate the problem. A sensitivity analysis was also performed, in which the influence of several parameters, such as fault resistance, system loading, detection threshold, fault type, and system expansion, was evaluated. The algorithm was validated in a Brazilian distribution system and in IEEE 34-bus system. The results indicated that the algorithm was able to detect voltage sags throughout the system using monitors at few buses, reducing the cost of the monitoring system.

【 授权许可】

CC BY   

【 预 览 】
附件列表
Files Size Format View
RO202108090001031ZK.pdf 1763KB PDF download
  文献评价指标  