Frontiers in Energy Research | |
Hybrid Simulation for Large-Scale AC/DC Power System by Serial Interaction Process | |
Shuguang Li1  Xintong Liu1  Guoqing Li1  Song Zhang2  | |
[1] Department of Electrical Engineering, Northeast Electric Power University, Jilin, China;null; | |
关键词: hybrid simulation; HVDC; transient stability; Thevenin equivalent; electromagnetic transient; | |
DOI : 10.3389/fenrg.2021.686566 | |
来源: Frontiers | |
【 摘 要 】
Electromechanical transient (EMT) and transient stability hybrid simulations can make full use of their fast-solving ability and high-precision computing ability to accurately simulate the dynamic characteristics of large-scale AC/DC systems. This paper selects the bus as the hybrid simulation interface bus in the AC system near the DC system, which can effectively improve the simulation accuracy of the AC/DC system interaction. At the interface bus, Norton equivalent and Thevenin equivalent are applied to the EMT simulation side and electromechanical transient simulation side, respectively. The three-phase simulation data and three-sequence component simulation data are extracted respectively, and the serial iteration method is used for hybrid simulation calculation. This paper takes Zhangbei multi terminal AC/DC system as an example, compares the hybrid simulation results with the EMT simulation results, and tries to verify the accuracy and effectiveness of the hybrid simulation method.
【 授权许可】
CC BY
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
RO202107123822718ZK.pdf | 764KB | download |