期刊论文详细信息
Engenharia Agrícola
Shewhart's control charts and process capability ratio applied to a sewage treatment station
Fábio Orssatto2  Marcio A. Vilas Boas1  Ricardo Nagamine1  Miguel A. Uribe-opazo1 
[1] ,UTFPR Núcleo de Ciências Biológicas e Ambientais Medianeira PR
关键词: STS;    Sewage;    Process Capability;    Shewhart Control Chart;    ETE;    Esgoto doméstico;    capacidade do processo;    cartas de controle;   
DOI  :  10.1590/S0100-69162014000400016
来源: SciELO
PDF
【 摘 要 】

The current study used statistical methods of quality control to evaluate the performance of a sewage treatment station. The concerned station is located in Cascavel city, Paraná State. The evaluated parameters were hydrogenionic potential, settleable solids, total suspended solids, chemical oxygen demand and biochemical oxygen demand in five days. Statistical analysis was performed through Shewhart control charts and process capability ratio. According to Shewhart charts, only the BOD(5.20) variable was under statistical control. Through capability ratios, we observed that except for pH the sewage treatment station is not capable to produce effluents under characteristics that fulfill specifications or standard launching required by environmental legislation.

【 授权许可】

CC BY   
 All the contents of this journal, except where otherwise noted, is licensed under a Creative Commons Attribution License

【 预 览 】
附件列表
Files Size Format View
RO202103040068197ZK.pdf 132KB PDF download
  文献评价指标  
  下载次数:1次 浏览次数:1次