期刊论文详细信息
Química Nova
Avaliação de diferentes métodos para a determinação de cobre em óleo mineral isolante por espectrometria de absorção atômica com forno de grafite
Luiz Fernando S. Caldas1  Carlos Eduardo R. De Paula1  Daniel M. Brum1  Fábio G. Lepri1  Ricardo J. Cassella1 
[1] ,Universidade Federal Fluminense Departamento de Química Analítica Niterói RJ ,Brasil
关键词: insulating oil;    copper;    GFAAS;   
DOI  :  10.5935/0100-4042.20140125
来源: SciELO
PDF
【 摘 要 】

This aim of this work was to compare two methods for copper determination in insulating oils from power transformers by GFAAS. The first method was extraction induced by emulsion breaking, which determined the preconcentration of copper in an aqueous solution and exhibited a limit of quantification of 0.27 µg L-1. Also, a second method based on the direct introduction of samples into GFAAS in the form of detergent emulsions, prepared with Triton X-114 and HNO3, was investigated. In this case, the limit of quantification was 1.7 µg L-1. Seven samples of used oils were successfully analyzed by both methods.

【 授权许可】

CC BY-NC   
 All the contents of this journal, except where otherwise noted, is licensed under a Creative Commons Attribution License

【 预 览 】
附件列表
Files Size Format View
RO202103040064538ZK.pdf 504KB PDF download
  文献评价指标  