Brazilian Journal of Chemical Engineering | |
Analytical approach based on a mathematical model of an air dehumidification process | |
D. Babakhani1  | |
[1] ,Islamic Azad UniversityFarahan,Iran | |
关键词: Dehumidification; Heat and mass transfer; HYSYS; | |
DOI : 10.1590/S0104-66322013000400011 | |
来源: SciELO | |
【 摘 要 】
In this paper we developed an analytical solution for a mathematical model of an air dehumidification process. This solution has good accuracy when compared with reliable experimental data available in the literature. The present study was confined to the cases with the mass flow rate of desiccant solution being much greater than the minimum required by the equilibrium calculation, so that the changes in the concentration and the flow rate are relatively small. Validation of this assumption has been performed by HYSYS software version 3.2. The influence of the Lewis number (Le) on the analytical results was considered. As shown in the current study, we obtain better results with Le=1.1 compared with Le=1. The benefits of the present solution are its simplicity and easy application for the simulation of air dehumidification.
【 授权许可】
CC BY
All the contents of this journal, except where otherwise noted, is licensed under a Creative Commons Attribution License
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
RO202005130129181ZK.pdf | 689KB | download |