期刊论文详细信息
Química Nova
Tratamento de águas de refrigeração com peróxido de hidrogênio
Fernando Antonio Serrapio Peres2  Luiz Alberto Cesar Teixeira1  Lídia Yokoyama1  Juacyara Carbonelli Campos1  Marco Antônio Lemos Miguel1 
[1] ,Instituto Nacional de Tecnologia Divisão de Corrosão e Degradação Rio de Janeiro RJ ,Brasil
关键词: cooling water;    corrosion;    biocide;   
DOI  :  10.1590/S0100-40422008000700042
来源: SciELO
PDF
【 摘 要 】

Hydrogen peroxide and chlorine are compared as possible disinfectants for water-cooling circuits. To this purpose, samples taken from the cooling system of a steel making plant were treated (at 25ºC and pH values of 5.5 and 8.5) with varying amounts of the two oxidizing agents (0.0 mg/L, 2.0 mg/L and 6.0 mg/L). The results were evaluated through bacterial counting and measurement of corrosion rates upon AISI1020 carbon steel coupons. Bacterial removal and corrosion effects proved to be similar and satisfactory for both reagents.

【 授权许可】

CC BY-NC   
 All the contents of this journal, except where otherwise noted, is licensed under a Creative Commons Attribution License

【 预 览 】
附件列表
Files Size Format View
RO202005130062592ZK.pdf 241KB PDF download
  文献评价指标  
  下载次数:17次 浏览次数:12次