期刊论文详细信息
Entropy
Optimal Cooling Load and COP Relationship of a Four-Heat-Reservoir Endoreversible Absorption Refrigeration Cycle
Lingen Chen1  Tong Zheng1  Fengrui Sun1 
[1] 1Faculty 306, Naval University of Engineering, Wuhan 430033, P.R. China 2Mechanical Engineering Department, U.S. Naval Academy, Annapolis, MD21402, USA
关键词: finite time thermodynamics;    thermodynamic optimization;    four-heat-reservoir endoreversible absorption refrigeration cycle;    optimal performance;   
DOI  :  10.3390/e6030316
来源: mdpi
PDF
【 摘 要 】

On the basis of a four-heat-reservoir endoreversible absorption refrigeration cycle model, another linear heat transfer law [i.e., the heat-flux] is adopted, the fundamental optimal relation between the coefficient of performance (COP) and the cooling load, as well as the maximum cooling load and the corresponding COP of the cycle coupled to constant-temperature heat reservoirs are derived by using finite-time thermodynamics or thermodynamic optimization. The optimal distribution of the heat-transfer surface areas is also obtained. Moreover, the effects of the cycle parameters on the COP and the cooling load of the cycle are studied by detailed numerical examples. The results obtained herein are of importance to the optimal design and performance improvement of an absorption refrigeration cycle.

【 授权许可】

CC BY   
This is an open access article distributed under the Creative Commons Attribution License (CC BY) which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

【 预 览 】
附件列表
Files Size Format View
RO202003190060582ZK.pdf 81KB PDF download
  文献评价指标  
  下载次数:4次 浏览次数:39次