期刊论文详细信息
Energies
Model for Predicting DC Flashover Voltage of Pre-Contaminated and Ice-Covered Long Insulator Strings under Low Air Pressure
Jianlin Hu1  Caixin Sun2  Xingliang Jiang2  Qing Yang2  Zhijin Zhang2 
[1] State Key Laboratory of Power Transmission Equipments & System Security and New Technology, College of Electrical Engineering, Chongqing University, Chongqing 400044, China;
关键词: ice-covered insulator string;    flashover;    mathematical model;    DC;    low air pressure;    pre-contamination;   
DOI  :  10.3390/en4040628
来源: mdpi
PDF
【 摘 要 】

In the current study, a multi-arc predicting model for DC critical flashover voltage of iced and pre-contaminated long insulator strings under low atmospheric pressure is developed. The model is composed of a series of different polarity surface arcs, icicle-icicle air gap arcs, and residual layer resistance. The calculation method of the residual resistance of the ice layer under DC multi-arc condition is established. To validate the model, 7-unit and 15-unit insulator strings were tested in a multi-function artificial climate chamber under the coexistent conditions of low air pressure, pollution, and icing. The test results showed that the values calculated by the model satisfactorily agreed with those experimentally measured, with the errors within the range of 10%, validating the rationality of the model.

【 授权许可】

CC BY   
© 2011 by the authors; licensee MDPI, Basel, Switzerland.

【 预 览 】
附件列表
Files Size Format View
RO202003190049662ZK.pdf 301KB PDF download
  文献评价指标  