Energies | |
Improving Transient Stability in a Grid-Connected Squirrel-Cage Induction Generator Wind Turbine System Using a Fuzzy Logic Controller | |
Minh Quan Duong1  Francesco Grimaccia1  Sonia Leva1  Marco Mussetta1  Kim Hung Le2  | |
[1] Politecnico di Milano, Dipartimento di Energia, Via La Masa 34, 20156 Milano, |
|
关键词: fuzzy logic; wind power; fault ride-through; squirrel-cage induction generator; transient stability; | |
DOI : 10.3390/en8076328 | |
来源: mdpi | |
【 摘 要 】
A common problem in wind power plants involves fixed-speed wind turbines. In fact, being equipped with a squirrel-cage induction generator (SCIG), they tend to drain a relevant amount of reactive power from the grid, potentially causing voltage drops and possible voltage instability. To improve SCIG power quality and transient stability, this paper investigates a new control strategy for pitch angle control based on proportional-integral (PI) controller and a fuzzy logic controller (FLC), considering both normal and fault ride-through (FRT) schemes. In the literature, often, the mechanical torque output is assumed constant for a specific wind speed. This might not be accurate, because the mechanical torque-speed typical of a wind turbine depends also on the power coefficient or pitch angle. In this paper, an analytic model of transient stability is proposed using the equivalent circuit of the SCIG and using the concepts of stable and unstable electrical-mechanical equilibrium. The method has been evaluated by comparing the results obtained by the analytic method with the dynamic simulation. The results show that the proposed hybrid controller is effective at smoothing the output power and complying with FRT requirements for SCIG in the power system.
【 授权许可】
CC BY
© 2015 by the authors; licensee MDPI, Basel, Switzerland
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
RO202003190010995ZK.pdf | 891KB | download |