Analysis of Short Time Period of Operation of Horizontal Ground Heat Exchangers
Salsuwanda Selamat1  Akio Miyara2  Keishi Kariya2 
[1]Graduate School of Science and Engineering, Saga University, 1 Honjo-machi, Saga 840-8502, Japan
[2]Department of Mechanical Engineering, Saga University, 1 Honjo-machi, Saga 840-8502, Japan
[3] E-Mails:
关键词: ground source heat pump;    ground heat exchangers;    numerical simulation;    horizontal;    slinky;   
DOI  :  10.3390/resources4030507
来源: mdpi
PDF
【 摘 要 】

Ground source heat pump (GSHP) systems have been proven to have higher efficiency compared to conventional air source heat pump systems for space heating and cooling applications. While vertical ground heat exchangers (GHE) are favorable in GSHP installation, this type of configuration requires higher capital costs as opposed to horizontal configuration. Numerical simulation has been used to accurately predict the thermal performance of GHE. In this paper, numerical analysis of thermal performance for slinky horizontal GHE loops in different orientations and operation modes is discussed. It was found that the loop orientation is not so important due to the little effect it has on thermal performance. While the mean heat exchange rate of copper loop increases 48% compared to HDPE loop, the analysis supports the common claim that heat exchange rate is predominantly limited by the thermal conductivity of the ground. With the same amount of circulation work, the mean heat exchange rate increases by 83%–162% when operated in parallel loops operations. The performance in these operations can be further optimized to 10%–14% increase when spacing between adjacent loops was provided. The spacing helps to minimize interference of heat flow that would penalize the overall thermal performance.

【 授权许可】

CC BY   
© 2015 by the authors; licensee MDPI, Basel, Switzerland.

【 预 览 】
附件列表
Files Size Format View
RO202003190009937ZK.pdf 1514KB PDF download
  文献评价指标  
  下载次数:4次 浏览次数:5次