JOURNAL OF CHEMICAL ENGINEERING OF JAPAN | |
Application of a Drag Reduction Phenomenon Caused by Surfactant Solutions | |
Takashi Saeki1  | |
[1] Department of Environmental Science and Engineering, Graduate School of Science and Engineering, Yamaguchi University | |
关键词: Air Conditioning System; Cooling Operation; Drag Reduction; Heat Transfer; Analogy; | |
DOI : 10.1252/jcej.13we086 | |
来源: Maruzen Company Ltd | |
【 摘 要 】
References(14)Cited-By(1)In 1994, the first commercial application of surfactant drag reduction was conducted in Japan for the air conditioning system in the Shunan Regional Industry Promotion Center building. A commercially available drag-reducing additive (LSP-01) based on the mixture of a cationic surfactant, a counter ion, and corrosion inhibitors was developed based on the results of the project. Since 1995, LSP-01 has been used at more than 180 sites in building air conditioning systems throughout Japan. The drag-reducing technique was adopted recently for an air conditioning system in a skyscraper in Tokyo. Here, I measured the drag reduction and heat transfer characteristics during the cooling operation of a heat exchanger for a surfactant and a counter ion system, Ethoquad O/12 and NaSal. The analogy between the momentum and heat transfer for the drag-reducing flow is also discussed.
【 授权许可】
Unknown
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
RO201912080697070ZK.pdf | 19KB | download |