Archives of Electrical Engineering | |
Induced sheath voltages in 110 kV power cables – case study* | |
Stanislaw Czapp1  Jacek Klucznik1  Zbigniew Lubosny1  Krzysztof Dobrzynski1  | |
关键词: electric shock hazard; induced voltages; power cables; power system; | |
DOI : 10.2478/aee-2015-0028 | |
来源: Versita | |
【 摘 要 】
This paper considers electric shock hazard due to induced sheath voltages in 110 kV power cables. The purpose of this paper is to find an optimal configuration of the power cable system, taking into account electric shock hazard and ability of the system to transfer maximal power. A computer simulations on a computer model of the local power system, comprising high voltage power cables, were carried out. This model enables to analyse various configurations of the metallic cable sheaths bonding and earthing (single-point bonding, both-ends bonding, cross-bonding) and their impact on induced voltages in the cable sheaths. The analysis presented in the paper shows, that it is possible to find an optimal configuration of the complicated power cable system, in terms of electric shock hazard, maximal power transfer as well as economic aspects.
【 授权许可】
Unknown
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
RO201912010188680ZK.pdf | 448KB | download |