Archives of Electrical Engineering | |
Efficiency comparison between the LLCL and LCL-filters based single-phase grid-tied inverters | |
Weimin Wu1  Min Huang1  Frede Blaabjerg1  | |
关键词: LCL-filter; LLCL-filter; efficiency power loss; modulation; single-phase grid-tied inverter; | |
DOI : 10.2478/aee-2014-0005 | |
来源: Versita | |
【 摘 要 】
An LLCL-filter is becoming more attractive than an LCL-filter as the interface between the grid-tied inverter and the grid due to possibility of reducing the copper and the magnetic materials. The efficiency of the LLCL-filter based single-phase grid-tied inverter also excites interests for many applications. The operation of the switches of the VSI is various with different modulation methods, which lead to different efficiencies for such a single-phase grid-tied inverter system, and therefore important research has been carried out on the effect of the choice of PWM schemes. Then power losses and efficiencies of the LLCL-filter and the LCL-filter based single-phase grid-tied inverters are analyzed and compared under the discontinuous unipolar, the dual-buck and the bipolar modulations. Results show that the efficiency of LLCL-filter based inverter system is higher than the LCL- filter based independent on the modulation method adopted. Experiments on a 2 kW prototype are in good agreement with results of the theoretical analysis
【 授权许可】
Unknown
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
RO201912010188611ZK.pdf | 2046KB | download |