Fire Science and Technology | |
Fire Tests in a Large Hall, Using Manually Applied High- and Low-Pressure Water Sprays | |
Stefan Svensson1  Stefan Särdqvist1  | |
[1] Swedish Rescue Service Agency, Revingeby, 247 81 Södra Sandby, Sweden | |
关键词: Large-scale extinguishing tests; Fire suppression; Fire fighting; Water; High-pressure; BA team; | |
DOI : 10.3210/fst.21.1 | |
学科分类:环境科学(综合) | |
来源: Tokyo University of Science * Center for Fire Science and Technology for Building | |
【 摘 要 】
References(25)Large-scale fire fighting was investigated, including a comparison between high-pressure and low-pressure manual fire fighting systems and measurements of heat stress on fire fighters. Six tests were performed in a room measuring 14.0 × 7.7 m². The fuel in each test consisted of wooden pallets arranged in 6 stacks with 13 pallets in each stack. Weight loss, gas temperature, heat radiation and room pressure were measured. The nozzle pressures were 7 bar and 25 bar and the flow rates were 1.92, 3.83 and 5.75 kg/s. The tests showed that the ability to reach the burning fuel with water limits the capacity of the fire-fighting attack. The high-pressure system proved more efficient than the low-pressure system. It gave a faster response and required a lower flow to attain the same extinction effect as the low-pressure system.
【 授权许可】
Unknown
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
RO201911300963380ZK.pdf | 3472KB | download |