期刊论文详细信息
American Journal of Applied Sciences
Comparison of Losses and Flux Distribution in 3 Phase 100 kVA Distribution Transformers Assembled from Various Type of T-Joint Geometry | Science Publications
S. Zakaria1  S. Taib1  S. Uthman1  Dina M.M. Ahmad1  I. Daut1 
关键词: Transformer core;    flux distribution;    rotational flux;    3rd harmonic flux;    power loss;    building factor (BF);   
DOI  :  10.3844/ajassp.2006.1990.1992
学科分类:自然科学(综合)
来源: Science Publications
PDF
【 摘 要 】

This paper describes results of an investigation of the variation of power loss, building factor, flux leakage and flux distribution in 3-phase model transformer cores assembled from various type of T-joint geometry. The loss of the core with T-joint 60o was 10%, 12% and 15% better than the core with T-joint 45o, T-joint 23o and T-joint 90o respectively and 1.7 T, 50 Hz. The flux lines showed that flux penetration into the central limb was an important factor in causing the differences in performance.

【 授权许可】

Unknown   

【 预 览 】
附件列表
Files Size Format View
RO201911300800343ZK.pdf 250KB PDF download
  文献评价指标  
  下载次数:5次 浏览次数:6次