American Journal of Applied Sciences | |
Supplying a Common Distribution Load through Two Different Sources | Science Publications | |
M. H. Naeem1  K. P. Basu1  | |
关键词: Power distribution; static phase shifter; tap changing transformer; power flow controller; | |
DOI : 10.3844/ajassp.2005.1305.1308 | |
学科分类:自然科学(综合) | |
来源: Science Publications | |
【 摘 要 】
Phase angle difference between any two Busbar voltages of a big power system varies with the loading and operating condition of the power system. Supplying a common distributed load from these two phase shifted sources needs the application of a controlled phase shifter. Three-phase tapped autotransformer connected in delta with properly controlled variation of input and output tap settings may perform the function of this type of phase shifter. Both on-load and off-load tap changing may be used to control the phase angle for scheduled sharing of a common distribution load between these two phase shifted sources. Independent control of voltage magnitude is also possible through the same phase shifter.
【 授权许可】
Unknown
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
RO201911300547927ZK.pdf | 95KB | download |